規格 | 容量KVA | 低壓側 | 高壓側 | 測量變化 | 60分鐘溫升℃ | 阻抗電壓% | 空載電流% | 質量kg | 外形尺寸長寬高mmmmmm | | 電壓V | 電流A | 電壓KV | 電流mA | | | 1.5/50 | 1.5 | 200 | 7.5 | 50 | 30 | 500 | 50 | 10 | <4 | 30 | 200275640 | | 3/50 | 3 | 200 | 15 | 50 | 60 | 500 | 50 | 10 | <4 | 35 | 240300690 | | 6/50 | 6 | 200 | 30 | 50 | 120 | 500 | 50 | 10 | <4 | 40 | 250355710 | | 10/50 | 10 | 200 | 50 | 50 | 200 | 500 | 50 | 10 | <4 | 60 | 260375750 | | 15/50 | 15 | 400 | 37.5 | 50 | 300 | 500 | 50 | 8 | <4 | 70 | 270420800 | | 20/50 | 20 | 400 | 50 | 50 | 400 | 500 | 50 | 8 | <4 | 85 | 285440820 | | 30/50 | 30 | 400 | 75 | 50 | 600 | 500 | 50 | 8 | <4 | 100 | 295386840 | | 50/50 | 50 | 400 | 125 | 50 | 1000 | 500 | 50 | 8 | <4 | 120 | 320416910 | | 10/100 | 10 | 200 | 50 | 100 | 100 | 1000 | 50 | 10 | <4 | 65 | 3504751300 | | 15/100 | 15 | 400 | 37.5 | 100 | 150 | 1000 | 50 | 8 | <4 | 85 | 5103901320 | | 20/100 | 20 | 400 | 50 | 100 | 200 | 1000 | 50 | 8 | <4 | 100 | 5404001340 | | 30/100 | 30 | 400 | 75 | 100 | 300 | 1000 | 50 | 8 | <4 | 110 | 5604101360 | | 50/100 | 50 | 400 | 125 | 100 | 500 | 1000 | 50 | 8 | <4 | 125 | 6004601410 | | 10/150 | 10 | 200 | 50 | 100 | 66.7 | 1500 | 50 | 10 | <4 | 90 | 2653801750 | | 15/150 | 15 | 400 | 37.5 | 150 | 100 | 1500 | 50 | 8 | <4 | 100 | 5103901800 | | 20/150 | 30 | 400 | 50 | 150 | 133.3 | 1500 | 50 | 8 | <4 | 110 | 5404151800 | | 30/150 | 30 | 400 | 75 | 150 | 200 | 1500 | 50 | 8 | <4 | 125 | 5604301800 | | 50/150 | 50 | 400 | 125 | 150 | 333.3 | 1500 | 50 | 8 | <4 | 140 | 6404901850 | |
YDQ-100KV充氣高壓試驗變壓器的使用條件: 1、試驗變壓器額定使用條件下應滿足下列要求: A、周圍環境溫度:最高氣溫+40℃最低氣溫-20℃ B、空氣最大相對溫度,當空氣溫度為25℃時,相對濕度不超過85%。 C、安裝地點無嚴重影響變壓器絕緣的氣體、蒸氣、化學性積塵,污垢及其它爆炸性介質的場所。 D、試驗變壓器使用時應使其輸入電壓逐步升高且應在輸出端串入足夠的保護電阻,切忌高壓狀態下斷合設備。 2、該變壓器允許運行時間。 在額定容量的額定電壓下,連續運行不得超過半小時,每次工作時間間隔為工作時間的5?-10倍,以保證變壓器的充分散熱,在額定電壓和額定電流的三分之二的工況條件下允許長期連續運行。技術指標及參數 1、對各電壓等級變壓器的空載電流4~9% 阻抗電壓4~10% 波形畸變5%氣體壓力:4.5MP |